How to choose a wire size
How the wire size is calculated
A ≥ ρ × 2L × I / (V × drop%)
AWG is a logarithmic scale: the bare diameter is d = 0.127 mm × 92^((36 − n)/39), so every 6 gauges halve the diameter and every 3 gauges halve the area. 18 AWG is 1.02 mm and 0.82 mm², 12 AWG is 3.31 mm². Metric cable is sold by its area directly: 0.75, 1.5, 2.5, 4, 6 mm²…
A wire’s resistance is R = ρ × length / area, with ρ = 1.72×10⁻⁸ Ω·m for copper (aluminium 2.82×10⁻⁸). Because the current goes out and back, the length is twice the distance to the load. The calculator finds the thinnest wire whose drop ΔV = I × R stays within your limit.
It then checks heating: the power I² × R warms the wire until convection and radiation carry it away. The size must keep the conductor under 60 °C in still 30 °C air; if that needs a thicker wire than the drop does, heat sets the size.
For PCB traces, IPC-2221 gives I = k × ΔT^0.44 × A^0.725 with the cross-section A in mil², k = 0.048 for outer layers and 0.024 for inner ones. Dividing the area by the copper thickness (35 µm per oz) gives the width.
Worked example: a 12 V LED strip 5 m away
A 12 V LED strip draws 5 A, 5 m from the power supply, and you accept a 3 % drop.
- Largest wire resistance allowed
12 V × 3 % / 5 A = 0.072 Ω - Smallest copper area (2 × 5 m of wire)
1.72e-8 × 10 m / 0.072 Ω = 2.39 mm² - 14 AWG is 2.08 mm²: too thin
drop ≈ 0.43 V = 3.6 % - 12 AWG is 3.31 mm²
drop ≈ 0.27 V = 2.3 %, loss ≈ 1.4 W
Use 12 AWG or 4 mm² wire: about 11.7 V reaches the strip and the wire stays close to room temperature.
Common mistakes
Counting only one wire
The return conductor has the same resistance as the positive one. Forget it and the real drop is twice what you planned.
Sizing a long low-voltage run by current alone
5 A is easy for 18 AWG over half a metre, but over 5 m at 12 V it drops almost 9 %. At low voltage the drop, not the heat, usually sets the size.
Reading AWG backwards
A bigger AWG number is a thinner wire: 22 AWG is for signals, 10 AWG for tens of amps. When between two sizes, take the smaller number.
Using free-air ratings in a bundle
Chassis-wiring tables assume one wire alone in air. Bundled in a loom or a conduit it runs much hotter: derate or go one size up.
Frequently asked questions
Compute the diameter d = 0.127 × 92^((36 − AWG)/39) mm, then the area π/4 × d². For example 14 AWG = 1.63 mm = 2.08 mm², close to the metric 2.5 mm².
18 AWG is 0.82 mm². The nearest metric size is 0.75 mm²; if the current is close to the limit, take 1 mm², which is the same or thicker.
As a single wire in free air, about 41 A (chassis wiring). As building wire in a conduit it is rated 20–30 A depending on the insulation, and for long low-voltage runs the voltage drop limits it much sooner.
3 % is a common target for power runs and LED strips, 5 % at most for most loads. USB devices need at least 4.75 V, so a 5 V supply leaves very little room.
Yes. Aluminium has about 1.64× the resistance of copper, so you need roughly 1.6× the area for the same drop, plus terminals rated for aluminium.
With 1 oz copper on an outer layer and a 10 °C rise, IPC-2221 gives about 0.30 mm (12 mil). An inner layer needs about 0.79 mm.








